Technical Data | |||||
Model | CE-3P75KEG | CE-3P80KEG | CE-3P90KEG | CE-3P100KEG | CE-3P110KEG |
Input (PV) | |||||
Recommended Max. PV Power (kWp) | 112.5 | 120 | 135 | 150 | 165 |
Max. Input Voltage (V) | 1,100 | ||||
Start-up Input Voltage (V) | 50 | ||||
MPPT Voltage Range (V) | 100~1,080 | ||||
Number of MPPTs | 7 | 9 | |||
String Number per MPPT | 2 | 2 | |||
Max. MPPT Input Current (A) | 7x40 | 9x40 | |||
Max. MPPT Short Circuit Current (A) | 7x60 | 9x60 | |||
Output(Grid) | |||||
Rated Output Power (kW) | 75 | 80 | 90 | 100 | 110 |
Max. Output Apparent Power (kVA) | 75 | 80 | 90 | 100 | 110 |
Max. Output Active Power (kW) | 75 | 80 | 90 | 100 | 110 |
Rated AC Voltage (V) | 220/380, 230/400, 240/415, 3L+N+PE | ||||
AC Voltage Range (V) | 312~520 | ||||
Max. Output Current (A) | 108.7 | 115.9 | 130.4 | 144.9 | 159.4 |
Rated Grid Frequency (Hz) | 50/60 | ||||
Grid Frequency Range (Hz) | 45~55/55~65 | ||||
Power Factor | >0.99, 0.8 leading~0.8 lagging | ||||
THDi | <3% | ||||
DC Current Injection | <0.5%ln | ||||
Efficiency | |||||
Max. Efficiency | 98.60% | ||||
European Efficiency | 98.30% | ||||
Protection | |||||
Ground Fault Monitoring | Support | ||||
Output Over Voltage Protection | Support | ||||
Anti-islanding Protection | Support | ||||
Intergrated AFCI | Optional | ||||
DC Reverse Protection | Support | ||||
Surge Arrester | DC Type II/ AC Type III | ||||
General | |||||
Topology | Transformerless | ||||
Ingress Protection | IP66 | ||||
Cooling | Smart fans | ||||
Operating Temperature Range(°C) | -25~+60 (>45 derating) | ||||
Relative Humidity Range | 0~100% (no condensing) | ||||
Max. Operating Altitude (m) | 3,000 | ||||
Noise Emission (dB) | <=40 dB(A) | ||||
Dimension (mm) | 1,020W×696H×300D | ||||
Weight (kg) | 85 | ||||
DC Connector | MC4/D4 | ||||
Communication | WiFi (2.4G), 4G, GPRS, Bluetooth, RS485 | ||||
Certification | |||||
Safety Standard | IEC 62109-1/-2, IEC 62477-1/-2 | ||||
EMC Standard | IEC 61000-1/-2/-3/-4 | ||||
Grid Code | AS4777.2, EN50549-1, G98, G99, ABNT NBR16149, ABNT NBR16150, VDE4105, CEI0-21, RD1699 |